Determination of Heat Load Distribution of Air Conditioning Unit for Official Rooms of Kirloskar Block at ITM University
International journal of scientific research in science, engineering and technology, 2017
In the present scenario due to the effect of Global warming. The temperature of the earth Increas... more In the present scenario due to the effect of Global warming. The temperature of the earth Increasing day by day which causes the requirement of Air conditioning for Domestic as well as official purposes .In this context, for the designing of air conditioning unit for office room of KIRLOSKAR block, ITM UNIVERSITY, GWALIOR. Complete calculation and analysis of heat load distribution inside an office has done, which include determination of total heat available inside the room due to internal as well as external heat sources. For designing of air conditioning unit of KRILOSKAR block having 30 official rooms (excluding laboratories), the heat load calculation has been done. A Single room of KIRLOSKAR blocks KB SF 315, (18040656) cm3, has been consider for determination of total heat load. After calculating the various sensible and latent heat load of room and outside air passing through room, it has been concluded that the Room sensible heat was 5676 W, Room latent heat was 995 W , Out...