TNB system is interconnected to Singapore PUB system via 230 kV tie Hines. The load and generation at Singapore PUB is assumed to be balance at 4000MW. Since the frequency decay rate is the function of percentage overload in the interconnected system, having the Singapore PUB connected would reduce the percentage overload and hence reduce the frequency decay rate. Fig. 2 shows the effect of tripping and not tripping the tie line to Singapore PUB in 6-stage scheme, The rate of frequency decay increase from 1.2 Hz/s to 2.3 Hz/s when the linc is tripped.

Figure 2 TNB system is interconnected to Singapore PUB system via 230 kV tie Hines. The load and generation at Singapore PUB is assumed to be balance at 4000MW. Since the frequency decay rate is the function of percentage overload in the interconnected system, having the Singapore PUB connected would reduce the percentage overload and hence reduce the frequency decay rate. Fig. 2 shows the effect of tripping and not tripping the tie line to Singapore PUB in 6-stage scheme, The rate of frequency decay increase from 1.2 Hz/s to 2.3 Hz/s when the linc is tripped.