Abstract
This paper addresses the CT saturation under severe fault in power system can be diagnosed and the DC component of the current can be identified. EMTP and ATP-based models are a convenient way of simulating fault transient for relay study. Compensation techniques achieve a significant reduction in the transient flux excursion in the core of a protective CT during the critical period of measurement, the first few half-cycles following fault incidence, thus preventing possible core saturation.
References (10)
- REFERENCES
- D.A.Bradley, C.B.Gray and D.O'Kelly, "Transients compensation of Current transformers", IEEE Trans. PAS, Vol. 97, No. 4, July/August 1978, pp. 1264-1271.
- S.H.Kang, S.H.Kang, J.K.Park, A.T.Johns, R.K.Aggarwal, "Development and hardware implementation of a compensating algorithm for the secondary current of current transformer", IEE Proc.- Electr. Power Appl., Vol. 143, No. 1, January 1996, pp. 41-49.
- Norman T.Stringer, "The effect of DC offsets on current operated relays", IEEE Transaction on Industry Applications, Vol. 34,No.1,January/February 1998, pp. 156-159.
- Kezunovic .M., Kojovic.L., Abur.A., Fromen.C.W., And Phillips.F., "Experimental evaluation of EMPT- based current transformer models for protective relay transient study", IEEE Trans. PWRD, Vol. 9, No. 1, January 1994, pp. 405-413.
- IEEE Power System Relaying Committee, "Transient Response of Current Transformers", IEEE Trans. PAS, Vol. 96, No. 6, November/December 1977, pp. 1809-1814.
- Q.Xu,A.Refsum,R.Watson,"Application of external compensation to current transformers", IEE Proc.-Sci.
- Meas, Technol., Vol. 143, no. 2, March 1996, pp. 147- 150.
- http//www.kilowatthours.com.html (Fundamentals of Current Transformer).